Heating reason of power cable in operation

When the power cable passes through a certain load current, it will be heated. With the increase of the load current, the cable surface temperature will be higher. If it is not handled in time, the consequences can be imagined. For example: PVC cable, the core temperature of 70 degrees is considered as the upper limit, and the surface temperature will be 5-10 degrees lower. Therefore, the cable surface temperature below 60 ℃ is basically safe. Considering the power supply maintenance, of course, the lower the temperature, the better.

The heating reasons of power cable in operation are as follows:

1. Cable conductor resistance does not meet the requirements, resulting in cable heating in operation.

2. Improper selection of cable leads to too small conductor cross-section of the cable used and overload phenomenon in operation. After long-term use, the imbalance of heating and heat dissipation of the cable causes heating phenomenon.

3. If it is too close to the cable, it may cause heat dissipation when the cable is too close to the cable.

4. Poor joint manufacturing technology and loose crimping will lead to excessive contact resistance at the joint and also lead to cable heating.

 

5. The insulation performance of cable phase to phase is not good, resulting in low insulation resistance and heating phenomenon during operation.

6. The partial sheath damage of armored cable will cause slow damage to the insulation performance after water inflow, resulting in the gradual decrease of insulation resistance, and also the heating phenomenon during the operation of the cable.

If the cause is not found out and the fault is eliminated in time, the insulation thermal breakdown will occur after the power cable is continuously energized. This will lead to phase to phase short-circuit tripping of cables, which may cause fire in serious cases.